IP67 or IP68 for Pressure Transmitters? Choosing Ingress Protection for Outdoor and Wet Duty

Choose IP67 or IP68 from rain exposure, water depth and duration, cleaning and assembly conditions. Outdoor use does not automatically require IP68. Match the rating to the model, pressure type, connector and complete installation. Do not change the measurement reference simply to obtain a higher ingress rating.

What the IP code actually means

DigitNumberMeaning
First (solids)6Dust-tight, no ingress of dust
Second (water)7Protected against the effects of temporary immersion
Second (water)8Protected against continuous immersion, more severe than 7

The IP code follows the enclosure-protection classification in IEC 60529. Digit 7 concerns temporary immersion and 8 immersion under specified conditions. Obtain the product’s depth, duration and assembly requirements. Cleaning jets, hot water and chemicals need separate suitability checks; IP68 alone does not qualify those duties.

Why one model carries two ratings

A relative gauge device needs a vent path to atmosphere, which adds a structural route to the outside and makes sealing harder than for absolute or sealed gauge designs. The usual pattern is:

Pressure typeConfiguration example (not a universal rule)Structural reason
AbsoluteIP68Reference cavity is a sealed vacuum; no venting needed
Sealed gaugeIP68Reference pressure sealed inside; no venting needed
Relative gaugeIP67Must communicate with atmosphere, adding a sealing path

PM160-E distinguishes gauge IP67 from absolute/sealed-gauge IP68. WA30 also specifies an M12 waterproof cable for its applicable IP68 versions. These are configuration-specific statements, not ratings for other models or arbitrary connectors.

The leak is rarely the housing

Sealing the enclosure is not the hard part. In long service, water usually enters at one of three places:

  1. Buttons and controls: check the sealing design and complete-assembly test evidence. A physical button is not automatically a leak path.
  2. Cable entry: inspect jacket, gland and end treatment. An unsuitable cable or seal can allow water to travel along conductors. Watertightness depends on the complete cable assembly; not all cables are inherently non-watertight.
  3. The process seal — a gasket material mismatched to temperature ages and fails.

WA30 display versions use an integrated magnetic switch that separates actuation from the internal electronics and avoids a conventional through-panel button opening. This reduces the associated button-seal leakage path. Long-term protection still depends on seals, connectors, assembly and environment; the switch does not guarantee IP68 throughout service life. Confirm the complete configuration and installation conditions.

Thermal cycling: the test that gets skipped

A static immersion test does not establish long-term reliability. Separately assess temperature cycling, seal ageing and cable strain. Request the relevant test method and report and consider retesting the final assembly. Do not claim a verified thermal-cycle count without the corresponding evidence.

Specifying by application

ApplicationRecommended ratingAssociated requirements
Indoor cabinet, dry workshopIP65 to IP67Confirm dust, cleaning and installation requirements
Outdoor equipment, exposed to rainBy actual exposureCable outlet facing down; seal the connector
Fire mains, pump rooms, below gradeCheck IP68 conditions if immersion is possibleRetain required pressure reference; confirm venting, connector and assembly
Submersible equipment, continuous immersionIP68Confirm depth, water quality, duration and complete assembly; not unlimited immersion

Checklist

  1. Pressure type: confirm whether local-atmosphere reference is required. Protection must be compatible with that reference; do not substitute another type solely for its IP rating.
  2. Confirm the connector — whether a waterproof type such as M12 is used and how the cable outlet is treated.
  3. Confirm whether there is a button — prefer magnetic or buttonless designs for display units.
  4. Seals: confirm the temperature range, medium compatibility and assembly conditions for the actual compound. NBR or FKM names do not establish one universal temperature rating.
  5. Confirm the verification method — whether waterproof retesting after thermal cycling was performed.

Next step

Compare WA30 display/magnetic-switch options for local inspection, PM350-RTU communications and power for distributed reporting, and PM160-E for industrial measurement. Check reference, range, ingress configuration and environment for each. An IP68 label alone does not qualify a device for any underwater duty.

More answers in the FAQ.

Similar Posts