RS PMLG150 is a compact submersible liquid level transmitter with MEMS piezoresistive sensing and fault diagnostics. Its modular, welded design supports water-level measurement in applications compatible with the wetted materials.
Digital compensation and calibration control measurement errors over the specified temperature band. EMI protection supports use in electrically noisy environments.
Full-scale level ranges run from 1 to 150 mH₂O, with ratiometric voltage, absolute voltage or 4–20 mA outputs. TEB and compensation bands depend on the selected level range, as shown below.
Features & Applications:
The RS PMLG150 is a fully sealed submersible smart liquid level transmitter built with an all-SUS316L stainless steel welded structure. It uses a high-performance, highly reliable piezoresistive pressure sensor made by Rodee Sensors and is manufactured with digital compensation and calibration, delivering high-accuracy level measurement across the full temperature range.
The cable is a high-quality waterproof cable with an air vent, connected to the stainless steel housing by a dual-sealing design to ensure long-term reliability when submerged. The 4-20 mA output version works on a two-wire loop. Thanks to its modular design, the product is compact, light, easy to install and reliable in use.
Product Highlights:

Specifications
| Parameter | Specification and conditions |
|---|---|
| Series | RS PMLG150 submersible liquid level transmitter |
| Full-scale level ranges | 1 to 150 mH₂O; select the ordering range |
| Signal output | 0.5–4.5 V ratiometric; 0–5 / 1–5 V and 0–10 / 1–10 V absolute voltage; 4–20 mA |
| TEB (full scale ≤3 mH₂O) | At 0 to 50 °C: typical ≤±0.25% FS, maximum ≤±0.50% FS |
| TEB (3<full scale≤10 mH₂O) | At 0 to 60 °C: typical ≤±0.20% FS, maximum ≤±0.25% FS |
| TEB (full scale >10 mH₂O) | At −10 to 70 °C: typical ≤±0.15% FS, maximum ≤±0.25% FS |
| Ambient operating temperature | Full scale ≤3 mH₂O: −10 to 70 °C; 3<full scale≤10 mH₂O: −20 to 80 °C; >10 mH₂O: −40 to 105 °C |
| Media and storage temperature | −40 to 105 °C; check ambient conditions against the selected range above |
| Supply | 0.5–4.5 V output: 5.0 VDC ±5%; other listed voltage outputs: 21–30 VDC; 4–20 mA: 10–32 VDC (24 VDC recommended) |
| 4–20 mA wiring and load | Two-wire loop; RL≤(SV−10 V)/0.022 A, including the entire measurement loop |
| Construction and wetted material | Welded SUS316L seal, anti-clogging structure, vented cable and dual-sealing design |
| Cable | Select length for installation depth and routing; match sheath material to the medium and environment |
| Datasheet version | 2026-04-23, 5 pages |